先分Chilled Ceiling System & Chilled Beam System
Chilled Ciling System, 就咁Laid啲Pipe响個Metal False Ceiling度,Cools Room by Natural Convection & Radiation, max. output only 70W/m² (*100ft/ton大概係380W/m²; 200ft/ton大概係190W/m²)
Chilled Beam System又分兩種,一種係Passive, 一種係Active
Passive 同Active 最大分別係,後者會比Pre treated Primary Air, 去到160W/m²
最重要設計考慮係唔好滴水,即係只要任何物件,包括個Fin, Ceiling Panel etc.個Surface Temperature高過Design個Dew Point, 就唔怕室內落雨。
上面堆資料見到,Primary Air 12℃, 入水15℃, Dew Point 13.5℃, 就避到滴水。
用呢種嘢好處係全部都係因為少咗Fan帶嚟,慳電、靜、慳維修,Ceiling Depth要求都少咗;
壞處係有水管响頭頂經過有機漏水,同埋如果啲Sensor / Control 做得唔好就兜頭落雨。此外Cooling Capacity都唔係高。
順帶一提仲有種係行Low Temperature Chilled Ceiling System, 個水溫用7℃, 但唔多案例,淨係得中國有相關Standard.
Example:
PAU駁住某堆Chilled Beam; Chilled Water 經Heat Exchanger派比Chilled Beam;
(鳴謝﹕紅豆)
想問圖入面個PHX係咩黎?
回覆刪除Plate Heat Exchanger
刪除