Design Considerations:
- 大量Toxic gas if not perfect combusion, e.g. Nitrogen Oxides (NOx), Carbon Monoxide (CO),EPD 出過指引唔可以超過某個限額
Design Strategies:
- EPD 出過個Scheme, 要隨時monitor住個NOx & CO level, 要收三個訊號,i) 正常Level, ii) Concertration 超標, iii) Fault/Failure, 如果濃度超標過四分鐘,就要即時踢起個ventilation system直至濃度回復正常水平;
- 用Jet Fan 射散啲空氣,operating cost慳過舖滿風管;亦可省卻某啲位Headroom for air duct as 可放陣void; 由上述CO sensor 踢郁,如圖
- EPD 要求25m之內要有一個CO sensor, 出/入口一定要有sensor;
- 再高階啲可以用CFD 模擬實際情況
- 除此之外Car Park 仲要留意EV Charger, Petrol Inteceptor Design
(鳴謝﹕紅豆; Source: EPD ProPECC PN 2/96)
(鳴謝﹕紅豆; Source: EPD ProPECC PN 2/96)
我想問下EPD 個scheme 可以係邊到搵到?
回覆刪除https://www.epd.gov.hk/epd/sites/default/files/epd/english/resources_pub/publications/files/pn96_2.pdf
刪除thanks ching!