Type 1: Single loop, constant flow,
Pressure sensor (installed in critical part) control bypass modulating valve, temperature sensor detect changing zone load and control 2 way valve.
For old or small building, 最舊式。
隨住時代既進步,VSD 同 Chiller技術都進步咗,以前舊樓冇用VSD, 個Chiller Evaporator 又唔可以Handle variable flow, 但上述問題都隨住時代進步而解決咗。而家一loop過搞掂,用嚟改裝Type 1, 即係Type 2 係 Type 1既升級版。
Type 2: Single loop with VSD,
Variable flow, pressure sensor (installed in critical part) control VSD, temperature sensor detect changing zone load and control 2 way valve. 條bypass 同埋個modulating valve唔洗再用。
For small building
Type 3, EMSD當年出過書仔叫大家用
Type 3: Primary & Secondary Loop, primary loop constant 可以令部chiller行得更穩定,secondary loop 行VSD. Keep primary loop constant flow, only need to consider primiary loop resistance (呢個講法可能有啲舊,我見Primary Loop都有VSD, 盡量令條by-pass flow rate 同Secondary 同步,但primary side 個flow點都大過secondary, 如果唔係return chilled water就會响條by-pass度同supply chilled water mix埋。Chiller evaporator 有個最低Limit, 大機50% 細機70%); Secondary loop use VSD to achieve variable flow with 2 way modulating valve, Primary loop 唔會受Secondary loop 既 arrangement 影响。
Primary Loop Size 大過或等於Secondary Loop, 原因為如果大唔過的話有機會條decoupler反流,到時相對高溫既水又流返入個coil度個2 way valve又會開盡,做成out of control (https://www.youtube.com/watch?v=9WeRclR1X_c)
而家可以再响Secondary Loop 度加一樣叫 "Predictive System Curve Controller" 既嘢,配合VSD使用。
原理 - Air terminal 駁住個2 way valve, 如果冇用呢舊嘢,當Air terminal 冷水需求降低時,個Valve就會收緊,同時多咗水經 by-pass. 用呢舊嘢目的係要同VSD配合,儘量開大個2 way valve從而降低系統既壓力,以達到節能效果。要做pricise commisioning.
For large building and variable load
![](https://blogger.googleusercontent.com/img/b/R29vZ2xl/AVvXsEhUt-yu8sODgnLEuxqUjq2YCYdhdJgWhpGMKwx1PhABE_JdLanOW48_tqIb6vY0q8A5F0UJ1MQzmS2ztLBSeDrKLpGUzW-Acy5FaJnPoSSn7DYnulAZog6Trx7dfacmrJBoTyAe4GazAIY/s640/2020-03-31_170236.jpg)
仲有種叫做Variable Primary Flow, Primary loop 有個Flow meter control bypass valve (其實同Type 2有啲乜本質上分別?除咗一個係Pressure Sensor control primary pump; 另一個係Flow Meter control bypass)
相對於Primary - Secondary, 好處包括裝少set Secondary Pump, lower initial cost; all pumps are VSD installed (P - S 組 Primary pump 係constant, 如果用量低的話就直接開泵又關泵, low load嗰陣optimize唔到pump energy). 壞處最主要係個Control複雜咗,同埋Chiller前要加isolation valve
![](https://blogger.googleusercontent.com/img/b/R29vZ2xl/AVvXsEg3EnRUp5yMBw5EUfvwQZ1TWKKENFCEcVF9Qs_RSgJF8e9hTAJbK2podPXcTX2ZY72KSDuNR9kINEoxGwqs3jT8Iwrod6swaxMp-qjDomCtW_pk9P2yAsQvOeV2Sh_gwkFBGXqBWArVmuA/s320/2020-07-02_153405.jpg)
Also reference: https://www.youtube.com/watch?v=-ahb6g3mrnE ; https://www.youtube.com/watch?v=41jRD61MW1o
----------------------------------------------------------------------------------------------------------------------
先講一般既water balancing. 每條Branch前都有隻Manual Balancing Valve 較水,由於chilled water去得遠啲,pressure head就會細啲,即係越近pump既branch就要較得實啲。
之後講Total Hydronic Balancing. 如果响某啲Branch度忽然個load好細,就會引致其他Branch個flow好大,咁隻控制Zone load既Modulating Control Valve就要較到好好好細,但細極有個極限,有啲類似VAV個Damper, 太細就會non linear characteristic out of control. 隻Differential Pressure Control Valve 就响呢個時候發揮作用,幫補隻Modulating Control Valve 收細個Flow, 從而比信號隻VSD令Motor減流速節能。
![](https://blogger.googleusercontent.com/img/b/R29vZ2xl/AVvXsEgr_o_EcPMw_WnjAZxDU2lViF3yrt8a9x6Va5m0oX_vmB1feFRhh-TfMsxPBS5W_VowQuoeFZ9XXDpjsFuLnScLZMcGBom93n3mpDicpHbuVMb8fN5VRfE9MiZadZfFeB6-eG9Ak-rl4nA/s640/2020-04-19_041538.jpg)
![](https://blogger.googleusercontent.com/img/b/R29vZ2xl/AVvXsEgyvX_I4gLgGED68u_fnJk-xQp4ccF1_x7l6D9yNkra1wxS0YQpA7bBxn6UQiQFxPc_rMmP7_SdHF07hKjroaGHbLeKY7gRJA4kmLHkg3_-FC1ilahmRfUSZ1RUKqBsPW5wK6-JOUd3biQ/s640/2020-04-19_041557.jpg)
(鳴謝﹕Kelvin Mak)
decoupler 個FLOW GE 流向係會隨住BUILDING LOAD 而變從而反映PART LOAD CONDITION
回覆刪除其實主要嘅principle喺balance兩邊loop個flow. 當Secondary loop flow大過primary loop時,deficit flow at bypass pipe就會產生。當個flow大到某程度set point時,primary loop嘅chiller and chilled water pump便會被trigger開多一台,目的就是increase翻primary loop個flow,從而達到Secondary loop所需求嘅flow. 此時,bypass pipe嘅flow會變成少許嘅surplus flow 或 trends to zero嘅flow. 當然,secondary loop個flow就是governed by啲control valves at Secondary loop嘅開關度而改變。而chilled water supply temperature to Secondary loop和load side對於indoor air temperature set point都是直接影響control valves嘅開關度。